ELIN DRS
Protective function settings MAIN II- (B)-F12TU16
 
Main Page
 
MAIN II- (B)-F12
DRS-ID:
TU16
DRS:
Dver 5.34 23.09.2008
DRS-WIN:
416, 128, 2414, 2414
Installed protective functions:
Signal Function 1
GCB OPEN
 MB111
Signal Function 1
FCB CLOSE
 MB111
 Voltage Balance 2
60P
 MU312
Current 3-ph.2-st.
50/51DB
 MI323
Current 3-ph.2-st.
50/51UAT
 MI323
Inv. Time Neg.Ph.Sequ.
46G
 MN322
Impedance 3-ph.
21G
 MZ322
Rev. Power 3-ph.1-st.
32G
 MP312
Frequency 4-st.
81G
 MF141
Overload 3-ph.
49G
 ML321
Page 1 of 142017-03-02 10:24
 
ELIN DRS
Protective function settings MAIN II- (B)-F12TU16
Protective function
Signal Function 1
GCB OPEN
MB111
Relay settings
Time Delay0.00 s  Active EdgeRising
Input matrix
Binary input SignalGCB OPENBlocking inputNot used
Page 2 of 142017-03-02 10:24
 
ELIN DRS
Protective function settings MAIN II- (B)-F12TU16
Protective function
Signal Function 1
FCB CLOSE
MB111
Relay settings
Time Delay0.00 s  Active EdgeRising
Input matrix
Binary input SignalFCB CLOSEBlocking inputNot used
Page 3 of 142017-03-02 10:24
 
ELIN DRS
Protective function settings MAIN II- (B)-F12TU16
Protective function
 Voltage Balance 2
60P
MU312
Relay settings
Operate Value I0.20 A Operate Value U20.5 V Time Delay3.00 s Phase RotationRight
Input matrix
Current input Phase A R- Gen. NeutralCurrent input Phase B Y-Gen. NeutralCurrent input Phase CB- Gen. Neutral Voltage input System 12U R-Y  Voltage input System 23U Y-B Voltage input System 31U B-R Test inputTEST 60PBlocking inputBLOCK 60P
Page 4 of 142017-03-02 10:24
of 14